ModuleDescriptionof170INT11000
20
4
Modiconprovidespre-fabricatedInterbuscablesinfourlengths.Eachcablehas
twoconnectorsinstalledfordirectinterconnectionbetweentwomodules.Modicon
alsoprovidesaconnectorkitforinstallationontouser-suppliedcable.Thekit
containsonepinandonesocketconnector(orderingdetailsseespecs).
Pleasenotethefollowinggeneralrequirements:
H Themaximumremote-buscablelengthis13km(8mi.).Thecablelength
betweentworemote-busnodesmustnotexceed400m(1200ft)!
H
Ready-madeoff-the-shelfcablesareavailablefortheremotebus:see
specs.Customlengthsneedtobepreparedbytheuser.
H Theconnectorsfortheoutgoingremotebusarealwayspins,thoseforthe
incomingremotebusarealwayssockets.
H Intheoutgoingremotebusconnector,pins5und9mustbeconnected(refer
toscematicthefigurebelow)!
H Connectthecableshieldtotheconnector.
H Fortheremotebusyouwillneeda5-wirecable,twisted-pairtype,shielded;
thiscableisavailablebythemeter(KAB-3225-LI).